Panoramic Power hardware

Hardware specifications

Wireless Sensors

Non-invasive, self-powered wireless current sensors for real-time energy monitoring. Clamp directly onto circuit wires with no rewiring, no downtime, no batteries. Data transmitted every 10 seconds.

Easy to install Self-powered Wireless connectivity High accuracy Multi-phase support
PAN-10 & PAN-12 Wireless Current Sensors
SpecificationPAN-10PAN-12
Dimensions17 × 20 × 32 mm (0.67 × 0.79 × 1.26 in)46.2 × 22.8 × 32.6 mm (1.82 × 0.90 × 1.28 in)
Max hot-wire diameter7 mm (0.28 in)18.8 mm (0.74 in)
Current range0 to 63 A0 to 225 A
Accuracy<2% at I > 3 A<2% at I > 10 A
Min operating current0.5 to 1 A (typical)0.7 to 1.2 A (typical)
AC frequency50 Hz (EU) / 60 Hz (US)
Transmission frequency434 MHz (EU) / 915 MHz (US)
Transmission power (ERP)0 dBm
Data interval10 seconds

PAN-14 Wireless High-Current Sensor
SpecificationPAN-14
Dimensions33.8 × 29 × 42.5 mm (1.33 × 1.14 × 1.67 in)
Current input range0 to 5 A, up to 10 A peak (from external CT)
Measurement rangeDetermined by external CT
Accuracy<2% at I > 0.1 A (input from CT)
Min operating current0.03 to 0.05 A (input from CT)
AC frequency50 Hz (EU) / 60 Hz (US)
Transmission frequency434 MHz (EU) / 915 MHz (US)
Transmission power (ERP)0 dBm (max)
Data interval10 seconds

PAN-42 Wireless Power Meter
SpecificationPAN-42
Voltage inputs4-wire Wye, 3-wire Delta, single-phase 3-wire, single-phase 2-wire, dual-phase 3-wire
Voltage levels120/208 V, 240/416 V, 277/480 V
Frequency range48 to 62 Hz
Current input range0 to 5 A, up to 10 A peak (from external CT)
Min measurable power0.025 W per phase
OutputsActive energy (kWh), true RMS voltage and current, active and reactive power, power factor, line frequency — all per phase
AccuracyANSI C12.1 Class 1 (CT class 0.2 or better)
Transmission frequency434 MHz (EU) / 915 MHz (US)
Transmission power (ERP)0 dBm (max)
Data interval10 seconds

Gen 4+ Bridge Connectivity Hub

Collects and transmits data from wireless sensors via Wi-Fi, Ethernet, or optional LTE. Supports Modbus TCP for third-party integration. Plug-and-play with remote firmware updates and built-in redundancy.

Plug-and-play Multi-network connectivity Data redundancy Field-upgradable firmware Modbus TCP integration
Physical & Power
SpecificationGen 4+ Bridge
Dimensions (without antennas)111 × 87 × 35 mm (4.4 × 3.4 × 1.4 in)
Weight (with antennas)150 g (0.33 lb)
Power adapter (included)Input: 100 to 240 VAC, 50 to 60 Hz / Output: 5 VDC
Power consumption5 W max
Connectivity & Communication
FeatureSpecification
Sensor receiver frequency915 MHz (US), 434 MHz (EU)
Sensor reception sensitivity-105 dBm
Cellular bands (LTE models)US: B2(1900) / B4(AWS1700) / B12(700)
EU: B1(2100) / B3(1800) / B7(2600) / B8(900) / B20(800) / B28A(700)
Wi-Fi protocol802.11 b/g/n
Wi-Fi securityWEP64, WEP128, WPA, WPA2, WPA2-Enterprise
Data compressionCollected and transmitted every 10 seconds
AuthenticationCHAP protocol
Pulse Interface
FeatureSpecification
Pulse inputs2x KY inputs
Voltage and current5 V open voltage, 0.9 mA max current
Pulse rate5 ms min pulse width, 100 Hz max rate
Product variants

Gen 4+ Bridge (LAN)

Ethernet and Wi-Fi connectivity

Gen 4+ Bridge (LTE)

Ethernet, Wi-Fi, and LTE with 3G fallback (US) / 2G fallback (EU)

RegionLAN modelLTE model
60 Hz regionsPAN-2-H-US V4+ (LAN)PAN-2-H-3G-US V4+ (LTE)
50 Hz regionsPAN-2-H-EU V4+ (LAN)PAN-2-H-3G-EU V4+ (LTE)

Certifications & Compliance

USA & Canada

SafetyUL 61010-1, UL 61010-2-030, CAN/CSA-C22.2 No. 61010-1 (ETL listed)
EMCFCC Part 15 Subpart B, ICES-003
RadioFCC Part 15 Subpart C, RSS-210, RSS-Gen
OtherPTCRB Listed

Europe & UK

SafetyEN 61010-1, EN 61010-2-030 (CE)
EMCEN ETSI 301 489-1, 301 489-3, 61326-1
RadioEN ETSI 300 220-1, 300 220-2

Other technical ratings

FlammabilityUL94 V-0
IP ratingIP5X
Operating tempPAN-10/14/42: -25 to 60°C / PAN-12: -25 to 50°C
Humidity5% to 95% non-condensing
Storage temp-25 to 65°C (-13 to 149°F)

CB scheme IEC 61010-1, IEC 61010-2-030 performed by Intertek Testing Services. In all other countries, local partners are responsible for product certifications.

See what your energy is really doing

Get device-level visibility across your operations and start identifying opportunities to reduce cost and improve performance.